Arc Fault Detection Device
MTAF5 / MTAF1
MTAF5 Arc Fault Detection RCBO device has the function of short circuit protection, overload protection, arc fault protection, and earth-leakage protection.
MTAF1-32 Arc fault Detection Device consists of a small circuit breaker, tripping mechanism, and arc detection module.
MTAF5 Arc-fault Detection Device (AFDD) Functions
Arc Fault Protection
Overload Protection
Short-circuit Protection
Earth-leakage Protection
Main Technical Parameters of MTAF5 |
||
Electrical Features |
||
Mode | Electronic | |
Type | A | |
Rated Current In | 6, 10, 16, 20, 25, 32, 40A | |
Poles | 1P+N | |
Rated Voltage Ue | 230V~ | |
Insulation Voltage Ui | 400V | |
Rated Frequency | 50Hz | |
Rated Residual Operating Current (I△n) | 30mA | |
Break Time Under (I△n) | ≤0.1s | |
Rated Breaking Capacity | 6,000A | |
Energy Limiting Class | 3 | |
Rated Impulse with Stand Voltage (1.5/50) Uimp | 4,000A | |
Dielectric Test Voltage at ind.Freq.for 1min | 2kV | |
Pollution Degree | 2 | |
Thermo-magnetic Release Characteristic | B | |
Mechnical Features |
||
Electrical Life | 4,000 Cycles | |
Mechanical Life | 10,000 Cycles | |
Contact Position Indicator | Yes | |
Protection Degree | IP 40 in Sentry MCU & Enclosures | |
Reference Temperature for Setting of Thermal Element | 30℃ | |
Ambient Temperature (with daily aver ≤ ℃) age 35 | -5℃ ~ +40℃ | |
Storage Temperature | -25℃ ~ + 55℃ | |
Installation |
||
Terminal Connection Type | Cable / Pin-typebusbar | |
Tightening Torque for L&N-LOAD | 2.5N㎡ | |
Tightening Torque (N*m) | 1.2N㎡ | |
Mounting | On Din rail EN60715(35mm) by means of fast clip device | |
Connection | Power supply from button |
MTAF1-32 Arc Fault Detection Device Overview
MTAF1-32 arc fault detection consists of a small circuit breaker, tripping mechanism, and arc detection module. MTAF1-32 have the function of short circuit protection, overload protection, and arc fault protection. It detects the arc fault through the chip detection program, and if it is confirmed as the fault arc, it will disconnect the power supply and provide arc fault protection. According to statistics, the proportion of total fire in electric fires is increasing year by year. In addition, seventy percent of electrical fires are caused by faulty arcs. MTAF3-32 arc fault protection device can effectively avoid fire caused by fault arcs.
MTAF1-32 AFDD Usage
MTAF1-32 AFDD are widely used in rated current 32A and the following household and similar communication circuits. arc fault protection unit of MTAF1-32 can detect and identify series arc faults, parallel arc faults, and ground arc faults. For example the old and damaged insulation layer of a line, wet air can cause arc faults phenomena. When Arc fault Detection Devices detect that there is arc faults exist, it would be automatically tripping and cut off the power supply.
Main Technical Parameters of MTAF1 |
|
Rated Working Voltage | AC 230V |
Rated Working Frequency | 50Hz±2% |
Rated Insulation Voltage | 400V |
Rated Impact Withstand Voltage | 4kV |
Rated Current | 6A、10A、16A、20A、25A、32A |
Number of Poles | 1P+N |
Type of Instantaneous Trip | B, C |
Short Circuit Capability | 6kA |
-